使用Sverker760进行漏电继电器注电测试

Perform Earth Leakage Injection Tests with Sverker760


Purpose:

How to perform Earth Leakage injection tests with Sverker760 to help ensure zero harm to people, community, the environment or business processes.

PPE:

Site PPE;LV rescue kit

Equipment:

Electricians toolkit;Sverker760 (04-00117);Jumper lead kit;Certified and calibrated multimeter

Materials:

Barricade tape and info tags;Camera;Torch

Task Preparation:

    1. Conduct a Take 5.

    2. Barricade area where testing will take place and place information tags.

    3. Ensure adequate communication and notice has been given to the people and/or parties that will be affected by the removal of power from the circuit to be tested.

Check that the circuit is OK to be tested

Familiarise Yourself with the Sverker760 Unit and Features you will be Using

The Sverker760 injection tests included in this SWI are:

    • Open CT Test.

    • Instantaneous Test.

    • Current Pick up Test.

    • Time Delay Test.

The current source built into the Sverker can provide 0-10A, 0-40A or 0-100A. Timing and generation outputs can be carried out at the same time. When the relay being tested trips, both output and timing are interrupted.


Sverker 760 

Push Button Test

1. Perform push button test on earth leakage (EL) relay to trip.

2. Confirm EL relay has tripped.

3. Open MCC enclosure and test for dead.

Valid CPR and LV rescue competencies are required for this task

Record Earth Leakage Relay Details and Settings

1. Record the EL relay’s make, type (ie. Ampcontrol, ELM) and serial number.

2. Record the trip level (mA) and the trip delay (ms) settings on the EL relay.

3. Inspect the connections and take a photo to later revert to original configuration.

Set up Sverker760

1. Check Sverker760 unit is within calibration date and power lead is tested and tagged.

2. Set up Sverker760 unit within reach of the EL relay.

3. Connect the leads as per below configuration steps.

Ensure LV rescue kit is complete and accessible and the work area is clear of trip hazards

Connection

1. Connect jumper lead from neutral current source to the ammeter current output as seen below.


Set up Sverker760

2. Connect jumper lead from the other ammeter current source to the bottom terminal of the resistor set as seen below.


Set up Sverker760

3.Connect jumper lead from the upper terminal of the resistor set, pass through the earth leakage toroid and connect to the 0-10 current output as seen below.

Set up Sverker760

4. Connect two jumper leads to the “STOP input” terminals as seen below. These leads will be connected to the shunt trip of the EL relay.

Set up Sverker760

5. Connect the other end of the jumper leads from the “STOP input” terminals (from previous step) to the shunt trip of the EL relay as seen in examples below.


Set up Sverker760

All connections are now finished and the circuit is complete.

Open CT Test

Valid CPR and LV rescue competencies are required for this task

Simulating an open circuit in the cabling to the EL toroid. This test shall result in a EL relay trip with a time of under 5s (AS2081 clause 6.4).

1. Turn on Sverker760.

2. Ensure the main knob on the Sverker760 is wound all the way to zero.

Press SEL button (marked A below the bottom right corner of the LED display) until the ammeter current output is selected. Ammeter current output LED labelled A will come on.


Open CT Test

If the EL relay does not trip during this test, Turn Sverker760 OFF and start again ensuring the EL relay is healthy and not showing a trip. Reset trip where necessary

3. Ensure the EL relay is healthy and not showing a trip. Reset if necessary.

4. Locate the UP arrow button on the Sverker760 located just below and to the left of the SEL button. Locate the terminals on the EL relay which go to the EL toroid.

SEL button

5. At the same time, pull out the EL toroid terminals from the EL relay and press the up button. The timer will start.

UP arrow button

6. The EL relay should trip within 5 seconds. The TRIP light and the OFF light on the Sverker760 will turn on and the ON+TIME light will turn off. Record the trip time (s) on the top left of the LED display.

Open CT Test

Instantaneous Test

The Instantaneous Test tests the minimum operating time of the EL relay and should be no greater than 50ms (AS2081 clause 6.3.2).

1. Ensure the OFF light next to the UP arrow on the Sverker760 is illuminated.

2. Ensure the main knob on the Sverker760 is wound all the way to zero.

3. Ensure the EL relay is healthy and not showing a trip. Reset if necessary.

4. Wind trip level (mA) and the trip delay (ms) settings on the EL relay down to the minimum.

5. Wind main knob on Sverker760 to 150% of the trip level (mA). (ie. if trip level is set at 100mA, wind knob up to 0.150A).

6. Press UP arrow to start test.

7. The EL relay should trip instantaneously. The TRIP light and the OFF light on the Sverker760 will turn on and the ON+TIME light will turn off.

8. Record the trip time (ms) on the top left of the LED display.

Instantaneous Test

9. Wind the main knob on the Sverker 760 back to zero.

10. Wind trip level (mA) and the trip delay (ms) settings on the EL relay back original positions.

11. Reset the trip.

Current Pick up Test

The Current Pick up Test tests the EL relay’s capability of accurately sensing and tripping a circuit where the fault current ranges from less than 0.1A up to 5A. The trip level (mA) result from this test should have an accurracy of +/-10% of the trip level setting (mA). (AS2081 clause 6.2).

1. Ensure the OFF light next to the UP arrow on the Sverker760 is illuminated.

2. Ensure the main knob on the Sverker760 is wound all the way to zero.

3. Ensure the EL relay is healthy and not showing a trip. Reset if necessary.

4. Press UP arrow to start test.

5. Slowly turn the main knob on the Sverker760 up until the EL relay trips. Once the EL relay trips, the TRIP light and the OFF light on the Sverker760 will turn on and the ON+TIME light will turn off.

Wind up main knob slowly

6. Record the trip level (mA) on the bottom left of the LED display. Ignore the trip time (s) for this test.

Current Pick up Test

7. Reset the trip.

Time Delay Test

The Time Delay Test tests the maximum delay time achievable by the EL relay associated with the trip level (mA) setting. The trip time (ms) result from this test should have an accurracy of -20% +0% of the trip time (ms) setting (AS2081 clauses 6.3.3 & 10.6.2.3).

1. Ensure the EL relay is healthy and not showing a trip. Reset if necessary.

2. Ensure the Sverker OFF light is illuminated and the ON+TIME light is off.

3. Wind the main knob on the Sverker760 up until the bottom left value on the LCD display shows 150% of the EL relay trip level (mA) (ie. if trip level is set at 100mA, wind knob up to 0.150A).

4. Press UP arrow to start test.

5. The EL relay should trip almost instantaneously. The TRIP light and the OFF light on the Sverker760 will turn on and the ON+TIME light will turn off.

6. Record trip time (ms) shown on the top left of the LED display.

Time Delay Test

7. Wind the main knob on the Sverker760 back to zero.

8. Reset the trip.

9. Turn Sverker760 off.

10. All Sverker760 injection tests are now complete.

Push Button Test

1. Once again, perform push button test on earth leakage (EL) relay to trip.

2. Confirm EL relay has tripped.

3. Reset trip

Review Results

1. Review results against acceptance criteria and notify supervisor of any EL relays that do not meet this criteria.

2. Discuss with supervisor and reliability engineer before altering any EL relay protection settings.

Return to Service

1. Remove tools and equipment.

2. Return EL relay settings and connections to original configurations.

3. Advise person in control of the area that the task is done and the equipment is available for return to service.

Complete job documentation and return to supervisor and advise task is done.

Standards

AS/NZS 3000 Wiring Rules

AS/NZS3007 (Electrical equipment in mines and quarries - Surface installations and associated processing plant)

AS/NZS2081 Electrical protection devices for mines and quarries

AS/NZS4871.1 Electrical equipment for mines and quarries - Part 1 General requirements

AS2225 Insulating gloves for electrical purposes

©著作权归作者所有,转载或内容合作请联系作者
  • 序言:七十年代末,一起剥皮案震惊了整个滨河市,随后出现的几起案子,更是在滨河造成了极大的恐慌,老刑警刘岩,带你破解...
    沈念sama阅读 204,189评论 6 478
  • 序言:滨河连续发生了三起死亡事件,死亡现场离奇诡异,居然都是意外死亡,警方通过查阅死者的电脑和手机,发现死者居然都...
    沈念sama阅读 85,577评论 2 381
  • 文/潘晓璐 我一进店门,熙熙楼的掌柜王于贵愁眉苦脸地迎上来,“玉大人,你说我怎么就摊上这事。” “怎么了?”我有些...
    开封第一讲书人阅读 150,857评论 0 337
  • 文/不坏的土叔 我叫张陵,是天一观的道长。 经常有香客问我,道长,这世上最难降的妖魔是什么? 我笑而不...
    开封第一讲书人阅读 54,703评论 1 276
  • 正文 为了忘掉前任,我火速办了婚礼,结果婚礼上,老公的妹妹穿的比我还像新娘。我一直安慰自己,他们只是感情好,可当我...
    茶点故事阅读 63,705评论 5 366
  • 文/花漫 我一把揭开白布。 她就那样静静地躺着,像睡着了一般。 火红的嫁衣衬着肌肤如雪。 梳的纹丝不乱的头发上,一...
    开封第一讲书人阅读 48,620评论 1 281
  • 那天,我揣着相机与录音,去河边找鬼。 笑死,一个胖子当着我的面吹牛,可吹牛的内容都是我干的。 我是一名探鬼主播,决...
    沈念sama阅读 37,995评论 3 396
  • 文/苍兰香墨 我猛地睁开眼,长吁一口气:“原来是场噩梦啊……” “哼!你这毒妇竟也来了?” 一声冷哼从身侧响起,我...
    开封第一讲书人阅读 36,656评论 0 258
  • 序言:老挝万荣一对情侣失踪,失踪者是张志新(化名)和其女友刘颖,没想到半个月后,有当地人在树林里发现了一具尸体,经...
    沈念sama阅读 40,898评论 1 298
  • 正文 独居荒郊野岭守林人离奇死亡,尸身上长有42处带血的脓包…… 初始之章·张勋 以下内容为张勋视角 年9月15日...
    茶点故事阅读 35,639评论 2 321
  • 正文 我和宋清朗相恋三年,在试婚纱的时候发现自己被绿了。 大学时的朋友给我发了我未婚夫和他白月光在一起吃饭的照片。...
    茶点故事阅读 37,720评论 1 330
  • 序言:一个原本活蹦乱跳的男人离奇死亡,死状恐怖,灵堂内的尸体忽然破棺而出,到底是诈尸还是另有隐情,我是刑警宁泽,带...
    沈念sama阅读 33,395评论 4 319
  • 正文 年R本政府宣布,位于F岛的核电站,受9级特大地震影响,放射性物质发生泄漏。R本人自食恶果不足惜,却给世界环境...
    茶点故事阅读 38,982评论 3 307
  • 文/蒙蒙 一、第九天 我趴在偏房一处隐蔽的房顶上张望。 院中可真热闹,春花似锦、人声如沸。这庄子的主人今日做“春日...
    开封第一讲书人阅读 29,953评论 0 19
  • 文/苍兰香墨 我抬头看了看天上的太阳。三九已至,却和暖如春,着一层夹袄步出监牢的瞬间,已是汗流浃背。 一阵脚步声响...
    开封第一讲书人阅读 31,195评论 1 260
  • 我被黑心中介骗来泰国打工, 没想到刚下飞机就差点儿被人妖公主榨干…… 1. 我叫王不留,地道东北人。 一个月前我还...
    沈念sama阅读 44,907评论 2 349
  • 正文 我出身青楼,却偏偏与公主长得像,于是被迫代替她去往敌国和亲。 传闻我的和亲对象是个残疾皇子,可洞房花烛夜当晚...
    茶点故事阅读 42,472评论 2 342

推荐阅读更多精彩内容